•Hydrants should be place at the corner of buildings that should the building collapse the hydrant is clear. • Pumper Nozzles shall be facing the street or access way. • Hydrants will be painted yellow with a blue bonnet. • Centerline of pumper nozzle shall be a minimum of 18 inches and a maximum of 22 inches above grade. • No obstructions with 7.5 feet to the front and sides and 4 …
o Fire hydrants need to be located within 50-feet and on the same side of the road with the Post Indicator Valve and Fire Department Connection (where required). o Where possible, fire hydrants should be located more than 40’ from structures. o Fire hydrants will be numbered with a unique identifier on all plans. This identifier will
Site Plan Fire Review Criteria Greensboro Fire …
Show all fire department connections on plan. 15. The fire hydrant shall face the fire department access roadway and shall be within six (6) feet of the curb line. 16. Fire hydrants shall be located no closer than forty (40) feet to any building that is being protected by that hydrant. 17. Fire Hydrants shall have one 4 ½ inch steamer nozzle, and two 2 ½ inch hose nozzles all with …
After a site analysis has taken place, your concept begins to take shape in the form of a site plan. It should clearly illustrate your current site and what you hope to create. It may include elements like dimensions, vegetation, weather, topography, and infrastructure. At My Site Plan, we help you bring your home addition and remodeling ideas …